Comparative measurement of surge arrester residual voltages by D-dot probes and dividers

I. A. Metwally

Research output: Contribution to journalArticlepeer-review

26 Citations (Scopus)

Abstract

This paper presents the design and testing of coaxial D-dot probes with three different designs, namely, totally closed, totally open and semi-open designs. The latter design gives a good response and has an easy-access assembly for fixing and replacing the surge arresters (SA) under test. Simultaneous measurements of residual voltage for 9-kV SA are conducted by the designed probes, and resistive and universal dividers (RD and MRCD). The divider compensation principle is also introduced and implemented for both dividers. Both perfectly compensated dividers and the designed D-dot probes have an error of about 2.5% in the SA residual voltage due to the unavoidable resistance of connecting leads. SA residual voltages measured by uncompensated short MCRD divider give good agreement with that measured by the D-dot probe. The former has small inductive overshoot which can be neglected as the residual voltage crests before the discharge current by a few microseconds.

Original languageEnglish
Pages (from-to)1274-1282
Number of pages9
JournalElectric Power Systems Research
Volume81
Issue number7
DOIs
Publication statusPublished - Jul 2011

Keywords

  • Arresters
  • Charge coupled devices
  • Impulse testing
  • Pulse generation
  • Voltage dividers
  • Voltage measurement

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Comparative measurement of surge arrester residual voltages by D-dot probes and dividers'. Together they form a unique fingerprint.

Cite this