Investigation of corona phenomenon for a reduced-scale model of hybrid AC and DC lines

I. A. Metwally*

*المؤلف المقابل لهذا العمل

نتاج البحث: المساهمة في مجلةConference articleمراجعة النظراء

4 اقتباسات (Scopus)

ملخص

A reduced-scale model of a single-phase ac (50 Hz) and a unipolar dc was developed with a suitable scaling factor where the applied voltages were varied up to 80 kV. Many factors were examined to show their effects on the I-V characteristics and on the corona current oscillograms. Also, a two-dimensional field computation program based on the charge simulation method (CSM) was used to model both the hybrid analog and an ac 132 kV double-circuit transmission lines in order to compute the ground-level electric field, number of streamers (for a constant time duration) and corona inception voltage for different arrangements and energization types and levels.

اللغة الأصليةEnglish
الصفحات (من إلى)610-613
عدد الصفحات4
دوريةConference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
مستوى الصوت2
حالة النشرPublished - 1996
منشور خارجيًانعم
الحدثProceedings of the 1996 Annual Conference on Electrical Insulation and Dielectric Phenomena. Part 2 (of 2) - Millbrae, CA, USA
المدة: أكتوبر ٢٠ ١٩٩٦أكتوبر ٢٣ ١٩٩٦

ASJC Scopus subject areas

  • ???subjectarea.asjc.2200.2208???
  • ???subjectarea.asjc.2200.2209???
  • ???subjectarea.asjc.2200.2215???

بصمة