Comparative measurement of surge arrester residual voltages by D-dot probes and dividers

I. A. Metwally

نتاج البحث: المساهمة في مجلةArticleمراجعة النظراء

26 اقتباسات (Scopus)

ملخص

This paper presents the design and testing of coaxial D-dot probes with three different designs, namely, totally closed, totally open and semi-open designs. The latter design gives a good response and has an easy-access assembly for fixing and replacing the surge arresters (SA) under test. Simultaneous measurements of residual voltage for 9-kV SA are conducted by the designed probes, and resistive and universal dividers (RD and MRCD). The divider compensation principle is also introduced and implemented for both dividers. Both perfectly compensated dividers and the designed D-dot probes have an error of about 2.5% in the SA residual voltage due to the unavoidable resistance of connecting leads. SA residual voltages measured by uncompensated short MCRD divider give good agreement with that measured by the D-dot probe. The former has small inductive overshoot which can be neglected as the residual voltage crests before the discharge current by a few microseconds.

اللغة الأصليةEnglish
الصفحات (من إلى)1274-1282
عدد الصفحات9
دوريةElectric Power Systems Research
مستوى الصوت81
رقم الإصدار7
المعرِّفات الرقمية للأشياء
حالة النشرPublished - يوليو 2011

ASJC Scopus subject areas

  • ???subjectarea.asjc.2100.2102???
  • ???subjectarea.asjc.2200.2208???

بصمة

أدرس بدقة موضوعات البحث “Comparative measurement of surge arrester residual voltages by D-dot probes and dividers'. فهما يشكلان معًا بصمة فريدة.

قم بذكر هذا