A three-phase fault currents calculation method used for protection coordination analysis

K. A. Saleh*, H. H. Zeineldin, A. Al-Hinai

*المؤلف المقابل لهذا العمل

نتاج البحث: Conference contribution

7 اقتباسات (Scopus)

ملخص

A reliable fault current calculation method is required to perform precise protection coordination analysis. The conventional short circuit calculation method is not valid for distribution power systems that are equipped with Inverter-Based Distributed Generation (IBDG) units. This paper proposes a new simple method based on the superposition theorem that calculates the three-phase fault currents for meshed distribution system in the presence of IBDG units. The proposed method is tested on the power distribution system of IEEE 14-bus with three IBDG units. The proposed method achieves good accuracy when compared to the results of a transient model of the test system. Moreover, the three-phase fault currents computed by the proposed method were used as part of the protection coordination problem. The protection coordination problem is formulated as a constrained non-linear programming problem and solved to determine the optimal relay settings.

اللغة الأصليةEnglish
عنوان منشور المضيفProceedings of the IEEE Power Engineering Society Transmission and Distribution Conference
ناشرInstitute of Electrical and Electronics Engineers Inc.
رقم المعيار الدولي للكتب (الإلكتروني)9781479936557
حالة النشرPublished - يوليو 23 2014
منشور خارجيًانعم
الحدث2014 IEEE/PES Transmission and Distribution Conference and Exposition, T and D 2014 - Chicago, United States
المدة: أبريل ١٤ ٢٠١٤أبريل ١٧ ٢٠١٤

سلسلة المنشورات

الاسمProceedings of the IEEE Power Engineering Society Transmission and Distribution Conference
رقم المعيار الدولي للدوريات (المطبوع)2160-8555
رقم المعيار الدولي للدوريات (الإلكتروني)2160-8563

Other

Other2014 IEEE/PES Transmission and Distribution Conference and Exposition, T and D 2014
الدولة/الإقليمUnited States
المدينةChicago
المدة٤/١٤/١٤٤/١٧/١٤

ASJC Scopus subject areas

  • ???subjectarea.asjc.2200.2208???

بصمة

أدرس بدقة موضوعات البحث “A three-phase fault currents calculation method used for protection coordination analysis'. فهما يشكلان معًا بصمة فريدة.

قم بذكر هذا